Partial Discharge’s Diagnostics for Detection of Electrical Equipment’s Faults, Defects

PDF

Published: 2021-06-14

Page: 86-98


Alexander Yu. Khrennikov *

Scientific Department, Scientific & Technical Center of Federal Grid Company of United Energy System, Russian Electrical Networks, Kashirskoe Highway, 22/3, 115201 Moscow, Russia.

Nikolay M. Aleksandrov

SPE Dynamics, 6 Anisimova Str., 428000, Cheboksary, Russia.

*Author to whom correspondence should be addressed.


Abstract

This paper presents an application experience of monitoring of the electric activity of the partial discharges (PD) in the insulation of transformers, data of electrical tests. The determination of partial discharges intensity was produced with the aid of the electrical method of PD registration. As the measuring means was used digital oscillograph, and also digital registrar-analyzer of the partial discharges. As a result the internal inspection of autotransformer windings after emergency switching off revealed the damage and short-circuit of the forth turns of regulating winding of 167 MVA/500/220 kV autotransformer. Methods and equipment for testing XLPE cables by ULF voltage (0.1-0.01 Hz) are also considered in the article.

Keywords: Partial discharges (PD), digital registrar-analyzer, electrical method of PD registration, internal inspection, autotransformer, XLPE cables, ULF for testing.